HVAC Manual J, S, D calculations: How to calculate them

Manual J, S, and D are critical HVAC design calculations used for properly sizing heating and cooling systems, selecting the right equipment, and designing ductwork for efficient air distribution.


1. Manual J – Load Calculation (Heating & Cooling)

Manual J: Calculates a building’s heating and cooling load to determine the required HVAC system capacity.

  • Determines the heating and cooling load of a building (how much heat needs to be added or removed).
  • Ensures the HVAC system is properly sized to avoid oversizing (energy waste) or undersizing (poor comfort).

How do I Perform Manual J Load Calculation?

Here’s a simple Manual J calculation example for a 1,000 sq. ft. house:

  • Location: Dallas, TX
  • House Size: 1,000 sq. ft. (single-story)
  • Insulation: R-30 in attic, R-13 in walls
  • Windows: Double-pane, 10% of floor area
  • Occupants: 3 people
  • Appliances & Lighting: Average usage
  • Infiltration: Moderate
  • Ventilation: ASHRAE standard

Cooling Load Calculation (Sensible + Latent Heat)

  • Walls & Roof (Conduction): ~8,000 BTU
  • Windows (Solar Gain): ~4,000 BTU
  • Infiltration & Ventilation: ~2,000 BTU
  • Occupants (Heat Load per person ~600 BTU): 3 × 600 = 1,800 BTU
  • Appliances & Lighting: ~2,200 BTU
  • Total Cooling Load: 18,000 BTU (~1.5 Tons)
  • Walls, Roof, & Windows (Heat Loss): ~12,000 BTU
  • Infiltration & Ventilation: ~3,500 BTU
  • Total Heating Load: 15,500 BTU (~1.3 Tons)
  • Choose an 18,000 BTU (1.5 Ton) Air Conditioner
  • Design a duct system to ensure proper airflow in each room

For precise results, HVAC software like Wrightsoft or Elite Software should be used.

  • Building Size & Layout (sq. ft, number of rooms)
  • Insulation Levels (walls, roof, windows, doors)
  • Climate Zone (local outdoor temperatures)
  • Windows & Doors (type, size, orientation)
  • Occupancy & Heat Gains (people, appliances, lighting)
  • Ventilation & Air Infiltration (leaks, fresh air needs)
  • Prevents oversized systems (higher costs, short cycling).
  • Ensures better comfort & humidity control.
  • Helps reduce energy bills.

Best for: Residential & light commercial HVAC sizing.


2. Manual S – Equipment Selection:

Manual S: Selects the appropriate HVAC equipment based on Manual J results, efficiency, and manufacturer specifications.

  • Uses Manual J results to select the right HVAC equipment (furnace, AC, heat pump).
  • Ensures equipment matches building loads for efficiency & longevity.

How do I Perform Manual S Calculation?

For a 1,500 sq. ft. home in Atlanta, GA:

  • Cooling Load (Total): 24,000 BTU (2 Tons)
    • Sensible Load: 18,000 BTU
    • Latent Load: 6,000 BTU
  • Heating Load: 36,000 BTU (3 Tons)

  • The selected unit should be no more than 15% larger for cooling.
  • Heating capacity should not exceed 40% of the Manual J load.

We check manufacturer specifications for an air conditioner & furnace:

Looking at a 2.5-ton (30,000 BTU) unit, its actual performance is:

  • At 95°F outdoor & 75°F indoor:
    • Total Cooling: 26,000 BTU
    • Sensible Cooling: 19,500 BTU
    • Latent Cooling: 6,500 BTU

Meets cooling needs (within 15% oversize limit)

A 40,000 BTU furnace has an 80% AFUE, meaning:

  • Usable heating output = 40,000 × 0.8 = 32,000 BTU
    Matches heating load closely (below 40% oversizing rule)

We confirm that the equipment:
✔ Matches Manual J loads
✔ Fits oversizing limits
✔ Provides efficient operation


  • 2.5-Ton Air Conditioner (26,000 BTU actual cooling)
  • 40,000 BTU Furnace (32,000 BTU output at 80% AFUE)

This ensures proper comfort, efficiency, and system longevity.

  • Cooling Capacity (BTUs & Tons) – Matches AC size to Manual J load.
  • Heating Capacity (BTUs) – Matches furnace or heat pump to Manual J results.
  • SEER & AFUE Ratings – Energy efficiency of cooling & heating equipment.
  • Latent vs. Sensible Heat Ratios – Ensures proper humidity control.
  • ✔ Ensures right-sized equipment (not just off-the-shelf units).
  • ✔ Improves efficiency & comfort.
  • ✔ Extends HVAC system lifespan.

📌 Best for: Choosing AC units, furnaces, heat pumps.


3. Manual D – Duct Design & Sizing:

Manual D: Designs the duct system to ensure proper airflow distribution based on Manual J and S calculations.

  • Designs the duct system to deliver correct airflow to each room.
  • Prevents pressure drop, noise, and airflow imbalances.

How to calculate Manual D?

For a 1,500 sq. ft. house with a 2.5-ton (30,000 BTU) AC unit:

  • Total Airflow Required: ~1,000 CFM (Cubic Feet per Minute)
  • Room-by-Room Cooling Load & Airflow Needs:
    • Living Room: 6,000 BTU → 200 CFM
    • Bedroom 1: 4,000 BTU → 130 CFM
    • Bedroom 2: 3,500 BTU → 115 CFM
    • Kitchen: 5,000 BTU → 170 CFM
    • Bathroom: 1,500 BTU → 50 CFM
    • Hallway: 2,000 BTU → 70 CFM
    • TOTAL: 1,000 CFM

Using 0.1 inches WC (Water Column) pressure drop per 100 ft and ideal air velocity (600-900 FPM for supply ducts), we size ducts:

RoomCFM NeededDuct Size (Round)Duct Size (Rectangular)
Living Room200 CFM8-inch6×10 inch
Bedroom 1130 CFM7-inch6×8 inch
Bedroom 2115 CFM6-inch6×6 inch
Kitchen170 CFM7-inch6×8 inch
Bathroom50 CFM5-inch4×6 inch
Hallway70 CFM6-inch6×6 inch

  • Air Handler Fan Capacity: 0.5 inches WC
  • Duct Resistance:
    • Supply ducts: 0.15 inches WC
    • Return ducts: 0.20 inches WC
    • Filter & Coil Losses: 0.10 inches WC
  • Total ESP = 0.15 + 0.20 + 0.10 = 0.45 inches WC ✅ (Acceptable under 0.5)

  • Return Ducts Size (matched to supply):
    • Main return = 12-inch round or 10×14 inch rectangular
    • Room returns sized to balance air distribution
  • Airflow Requirements (CFM per room) – Based on Manual J results.
  • Duct Sizing & Layout – Determines duct diameter for proper airflow.
  • Static Pressure Calculation – Ensures the fan can push air effectively.
  • Friction Losses & Velocity – Balances airflow speed to avoid noise.
  • Prevents hot & cold spots.
  • Reduces fan energy consumption.
  • Ensures quiet & efficient airflow.

📌 Best for: Designing new duct systems or improving existing HVAC airflow.


4. How Manual J, S, and D Work Together:

1️⃣ Manual J → Determines heating & cooling loads (how much capacity is needed).
2️⃣ Manual S → Selects the right HVAC equipment based on Manual J results.
3️⃣ Manual D → Designs the duct system to distribute air properly.

Manual J says a home needs 4 tons of coolingManual S selects a 4-ton AC unitManual D designs the ducts to distribute air evenly.

Final Result:

  • Properly sized HVAC system
  • Better comfort & efficiency
  • Lower energy costs

What is the Difference between Manual J,S and D in HVAC?

ManualPurposeKey Focus
Manual JLoad CalculationDetermines how much heating/cooling a home needs.
Manual SEquipment SelectionMatches HVAC units to the home’s load requirements.
Manual DDuct DesignEnsures proper duct sizing for balanced airflow.

  • Manual J: Calculates a building’s heating and cooling load to determine the required HVAC system capacity.
  • Manual S: Selects the appropriate HVAC equipment based on Manual J results, efficiency, and manufacturer specifications.
  • Manual D: Designs the duct system to ensure proper airflow distribution based on Manual J and S calculations.